A brewery may discharge most of its wastewater during the day, but the anaerobic reactor can keep producing biogas after the production line shuts down at night. If the boiler is idle, where does that biogas go? And when the boiler starts up again, can biogas production keep pace with the rise in demand?
That is why many breweries with anaerobic wastewater treatment systems install double membrane gas holders. A gas holder stores surplus biogas and releases it when downstream equipment needs it, allowing wastewater treatment and energy recovery to operate on different schedules.
Breweries generate wastewater during mashing, fermentation, equipment cleaning, and packaging. This wastewater contains residual sugars, yeast, and other organic matter. After pretreatment and flow equalization, it can be fed into an anaerobic reactor, such as an upflow anaerobic sludge blanket (UASB) reactor. Microorganisms break down the organic matter, reducing the wastewater’s organic load while producing biogas composed mainly of methane and carbon dioxide.
The anaerobic effluent proceeds to further treatment. The recovered biogas can be desulfurized and dried as required before being used in a boiler or a combined heat and power (CHP) unit. The double membrane gas holder provides storage, buffering, and pressure stabilization in this process.
Brewery wastewater discharge varies with production batches, cleaning schedules, and shifts. Biogas output also depends on the incoming organic load and the operating conditions of the anaerobic system. Meanwhile, boiler gas consumption follows steam demand, and generators have their own start-up, shutdown, and maintenance schedules. Biogas production and demand rarely match throughout the day.
When production exceeds demand, the gas holder stores the surplus, reducing the need to send short-term excess gas to the flare. When demand temporarily exceeds production, the gas holder releases stored biogas to supplement the supply to a boiler or generator. It also helps dampen pressure fluctuations in the gas network, giving downstream pressure regulation and gas delivery a steadier inlet pressure.
Gas holder capacity should therefore be sized around the biogas production profile, the gas consumption schedule, and the longest planned outage of the gas-consuming equipment. Two breweries with the same wastewater treatment capacity may need different storage volumes if one runs its boiler continuously while the other uses most of its gas during the day.
![]()
A freestanding double membrane gas holder consists of an outer membrane, an inner membrane, and a bottom membrane. The inner membrane rises and falls as the amount of stored biogas changes, varying the volume of the gas chamber. An air blower supplies air to the space between the inner and outer membranes. This keeps the outer membrane in shape, while regulating the air pressure in that space helps stabilize the biogas storage pressure. The bottom membrane and the perimeter anchoring and sealing system form a gas-tight base.
This design is suited to low-pressure biogas storage with a variable gas volume. The membranes can be prefabricated at the factory, leaving foundation checks, membrane installation, anchoring and sealing, and commissioning of the piping and controls for the site team. A brewery adding biogas recovery to an existing wastewater treatment plant can locate a freestanding gas holder around the available space and existing piping. A tank-mounted gas holder, by comparison, must be designed to suit the tank structure and roof connections.
Qingdao Haiyue supplied a 100 m³-class double membrane gas holder for the Blue Ribbon Brewery wastewater treatment project in Sanya, Hainan. The usable storage volume was selected to suit the project’s needs and buffer the biogas produced by the anaerobic treatment system. Because the brewery is on the coast, salt spray, UV exposure, and wind loads were taken into account during design and installation.
The work covered membrane and anchor selection, site layout checks, perimeter fastening, leak testing, and commissioning of the pressure and vacuum protection devices. Each step helped integrate the gas holder with the brewery’s existing wastewater treatment and biogas utilization systems. At handover, the site team received training on equipment operation and routine inspections.
For a brewery, the value of a double membrane gas holder shows up in daily operation. It stores biogas when demand is low and supplies it when demand rises. That means more of the gas recovered from wastewater can be used to generate heat or electricity for the plant.
If you are planning an anaerobic treatment or biogas recovery project for brewery wastewater, share your expected biogas output, gas-consuming equipment and operating schedule, site conditions, and target supply pressure with Qingdao Haiyue. We can help determine the right storage capacity, installation configuration, and supporting equipment for your project.